Therma-HEXX supplies the whole hydronic system, not just the panels. Every ThermaPANEL and ThermaCEILING job ships with the manifolds, circulators, heat exchanger where one is needed, air and dirt separation, expansion and glycol feed sized for that job, from manufacturers we hold OEM accounts with: Caleffi, Taco Comfort Solutions, Grundfos, Spirotherm, Axiom, Amtrol, Chiltrix and Belimo. Snowmelt controls from OJ Electronics are part of the package. Loxone and Tekmar are specified for the integrator or installer to supply. One schematic, one supplier, one phone number when the plumber has a question.

Why we supply the package
A radiant panel is only as good as the fluid delivered to it. Most field problems we have seen in twenty years were not panel problems: an undersized circulator, air in a high point, a boiler loop with ferrous components dumping oxide into a nonferrous system, a mixing valve that could not hold a setpoint above dew point. Supplying the parts we have already sized removes the guesswork for the installer and the finger pointing afterward. The plumber connects what arrives on the pallet to the heat source, fills and tests to our instructions, and the system runs as designed.
What is in the package
| Part | Supplier | What it does in a Therma-HEXX system |
|---|---|---|
| Manifolds and balancing | Caleffi | Supply and return manifolds with flow meters and balancing valves, so each panel row gets its design flow. Zone valves where zones are separately controlled. |
| Circulators | Taco Comfort Solutions, Grundfos | ECM circulators sized to the system’s flow and head. Taco 0034ePLUS and VR series and Grundfos equivalents communicate with the controls over Modbus; stainless bodies on glycol systems. |
| Heat exchangers | Taco Comfort Solutions, Caleffi | Brazed plate exchangers that separate a building hot water loop, boiler loop or ferrous system from the glycol loop serving the panels. Sized to the design approach temperature. |
| Air and dirt separation | Spirotherm, Caleffi | Spirovent air eliminators and dirt separators keep air out of panel rows and magnetite out of circulators and valves. |
| Expansion and pressure | Amtrol | Expansion tanks sized to the system volume and glycol percentage; pressure relief and fill assemblies. |
| Glycol feed | Axiom | Automatic glycol feeders that hold system pressure with premixed inhibited propylene glycol instead of a potable water make up, which would dilute the glycol over time. |
| Mixing and dew point control | Belimo | Spring return motorized three way valves temper the supply to a setpoint. On ThermaCEILING the valve holds the ceiling above dew point and fails to the safe position if power drops. |
| Heat pumps | Chiltrix | Air to water heat pumps for heating, cooling and snowmelt from one unit. Modbus communication with the controls; AHRI certified ratings published. Two New Hampshire houses, in Jaffrey and in Rye, heat and cool the interior and melt the exterior surfaces from the same Chiltrix units. |
| Interior controls (specified, supplied by the integrator) | Loxone | Cloud free building controller that runs heat pump, circulators, mixing valves, dehumidification and ventilation as one system, with weather based dew point prediction. Loxone page. |
| Snowmelt controls | OJ Electronics (supplied); Tekmar (specified) | Surface sensing snow and ice controls that start the system when the sensor sees moisture and freezing together and stop it when the surface is clear, as the energy codes require. |
Boilers are by others. We size the load and the exchanger to whatever boiler, chiller or heat pump the project uses. We supply OJ Electronics snowmelt controls; where the project calls for Loxone or Tekmar we write the control specification and the integrator or installer supplies it.

How it arrives
With the panel rows, boxed and labeled to the layout drawing, and a schematic that shows where each part goes. The installer follows the installation manual and the fill, test and maintenance instructions. We answer the phone during the install, and for a crew’s first ThermaPANEL job we can send an onsite trainer for the start of it. Typical plumbing diagrams are on the resources page.

Send us the plans
The heated area, the surface, the heat source you have in mind and the mechanical room location. We return the layout, the BTU estimate, the mechanical schematic with the package listed, and the controls specification. Contact Therma-HEXX engineering or call (603) 319-8815.
Questions
Can I buy the panels alone and source the rest myself?
You can, and some contractors do. We still provide the sizing. Most choose the package because the parts arrive matched and the warranty conversation is with one company.
Does the system need a heat exchanger?
When the heat source loop has ferrous components, when the boiler manufacturer requires one, or when a building loop must stay separate from the glycol. Otherwise the system can run as one nonferrous loop.
What glycol?
Inhibited propylene glycol, premixed, at a percentage set for the project’s location per ASHRAE. The Axiom feeder keeps it that way.
Which heat pumps work?
Any air to water or water to water heat pump that delivers the design supply temperature, 100 to 130 F for snowmelt and lower for ThermaCEILING heating. We supply Chiltrix and have worked with others.
